Toshiba H9 Installation And Operation Manual page 205

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

F683
FM Bias Adjustment
Program ⇒ Terminal ⇒ Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the FM terminal.
Set the function of
F005
to zero and then set this parameter to zero for proper
operation.
See
F005
for more information on this setting.
AM Output Gradient Characteristic
Program ⇒ Terminal ⇒ Analog Output Terminals
This parameter sets the output response polarity of the AM output terminal.
The AM output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See
F670
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
AM Bias Adjustment
Program ⇒ Terminal ⇒ Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the AM terminal.
Set the function set at
F670
proper operation.
See
F670
for more information on this setting.
MON 1 Voltage/Current Output Switching
Program ⇒ Terminal ⇒ Analog Output Terminals
This parameter is used to set the output signal type of the MON1 output
terminal.
Settings
0 — -10V – +10V
1 — 0 – 10V
2 — 0 – 20 mA
MON 1 Output Gradient Characteristic
Program ⇒ Terminal ⇒ Analog Output Terminals
This parameter sets the output response polarity of the MON1 output terminal.
The MON1 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter
F672
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
H9 ASD Installation and Operation Manual
to zero and then set this parameter to zero for
Direct Access Number — F683
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — +100.0
Units — %
Direct Access Number — F685
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
Direct Access Number — F686
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — +100.0
Units — %
Direct Access Number — F688
Parameter Type — Selection List
Factory Default — 0 – 10V
Changeable During Run — Yes
Direct Access Number — F689
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
F689
197