Pid Output Lower Limit; Process Increasing Rate; Process Decreasing Rate; Number Of Pg Input Pulses - Toshiba H9 Installation And Operation Manual

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

F371

PID Output Lower Limit

Program ⇒ Feedback ⇒ Feedback Settings
Selecting Speed PID at parameter
function as the Lower Limit while operating in the PID Control mode.

Process Increasing Rate

Program ⇒ Feedback ⇒ Feedback Settings
This parameter is used to limit the rate that the output of the ASD may increase
for a given difference in the speed reference and the PID feedback value.

Process Decreasing Rate

Program ⇒ Feedback ⇒ Feedback Settings
This parameter is used to limit the rate that the output of the ASD may decrease
for a given difference in the speed reference and the PID feedback value.

Number of PG Input Pulses

Program ⇒ Feedback ⇒ PG Settings
This parameter is used to set the end-of-travel range when using an encoder on
a motor-driven positioning system (e.g., hoist/crane, etc.).

Number of PG Input Phases

Program ⇒ Feedback ⇒ PG Settings
This parameter determines the type of information that is supplied by the phase
encoder.
Settings:
1 — Single Phase
2 — Two Phase
150
F359
allows for this parameter setting to
Direct Access Number — F371
Parameter Type — Numerical
Factory Default — 4.00
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Direct Access Number — F372
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Direct Access Number — F373
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Direct Access Number — F375
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — No
Minimum — 12
Maximum — 9999
Direct Access Number — F376
Parameter Type — Selection List
Factory Default — (ASD-dependent)
Changeable During Run — Yes
H9 ASD Installation and Operation Manual
F376

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents