Itemized setting screen 4/5
Itemized setting screen 5/5
5) Hysteresis
・Set hysteresis to be used at A channel, B channel and 2 channel.
・Set it on the 10-key input screen.
・For 2 channel, use the HI Hysteresis set value and LO Hysteresis set value
for each channel.
・When "Area" or "Rank" are selected as Comparison output type (Type) on
6), some setting conditions are provided.
(For details, refer to「10-2. 2) Area type (Area), 3) Rank type (Rank)」)
* When Comparison output type (Type) setting is "Normal" and the
Comparison output type (Type) is changed into "Area" or "Rank", without
fulfilling the setting conditions, the 10-key input value of hysteresis may not
be reflected.
In such a case, return the Comparison output type (Type) to "Normal" once,
and change the Comparison output type (Type) into "Area" or "Rank" after
entering the set value
・Setting range : ±9999
HH hysteresis set value (HH Hysteresis)
HI hysteresis set value (HI Hysteresis)
LO hysteresis set value (LO Hysteresis)
LL hysteresis set value (LL Hysteresis)
6) Comparison output type (Type)
・Set a Type of comparison output (Type) on t he set-value select screen.
・Setting items
(1) Normal
(2) Area
(3) Rank
7) Zero Band
・Set Zero Band on the 10-key input screen.
・Setting range : 0 to 99999
・The indicated value and Zero band set value are checked during operation.
At the |indicated value| > the Zero band set value, it is judged as the
outside of the Zero band range.
The result of check is used on the Comparison output start conditions
(Start Condition) given in the next paragraph.
8) Comparison output start conditions (Start Condition)
・Set the output start conditions to be output on the set-value select screen.
・Setting items :
(1) Always
(2) Zero Band
(3) Motion
(4) (2) + (3)
(Z + M)
(For description of (3) Motion, refer to 4) of「6. Basic Function Setting
(Setup)」.)
For contents of operation, refer to
「10. Comparison Operation」.
Always output.
Outputs at outside of zero band range.
Outputs, when motion is stable on display.
Outputs, when indicated value is stable and
outside Zero band range.