Chassis Airflow
S e n d d o c u m e n t c o m m e n t s t o n e x u s 7 k - d o c f e e d b a c k @ c i s c o . c o m
Figure A-16
1
Airflow for cooling the supervisor and I/O
modules
2
Airflow for cooling the fabric modules
To allow for the Cisco Nexus 7009 and 7018 switches to take in air from the cold aisle and floor on the
right side, you should route cables on the left front side of the switch. If necessary, you can route cables
on the upper right front side of the chassis, which leaves the lower right side open to cooling air from
the cold aisle in front of the chassis. By having the cables on the left side and leaving the left rear side
unobstructed, the exhaust is directed to the hot aisle in back.
For the clearances required on each side of the switch, see the
page
A-14.
To determine the maximum amount of airflow for a fully configured switch, see
Nexus 7009 switch, see
Nexus 7018 switch.
Systems with fewer than the maximum number of supervisor, I/O, or fabric modules will have less
Note
airflow.
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
A-18
Airflow for the Cisco Nexus 7018 Chassis
Table A-16
for the Cisco Nexus 7010 switch, or see
Appendix A
3
Airflow for cooling the power supply units
"Chassis Clearances" section on
Table A-17
Technical Specifications
Table A-15
for the Cisco
for the Cisco
OL-23069-06

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nexus 7009Nexus 7018Nexus 7010

Table of Contents