Table: 14 Process Image Configuration For Ni 120, With Broken Wire Diagn - WAGO -I/O-SYSTEM 750 750-481/003-000 Manual

2ai rtd ex i 2-channel analog input module for resistance sensors, ex i
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-481/003-000 2AI RTD Ex i

Table: 14 Process Image Configuration for Ni 120, with broken wire diagn.

Temperature
°C
<-80.0
-80.0
-50.0
0.0
50.0
100.0
150.0
200.0
250.0
300.0
320.0
>320.0
Broken wire
against RL
1) Temperature values below 0 °C are represented in two's complement binary form.
The measured value can exceed the range from –800 to 3200 until the limitation
applies.
Manual
1.1.0
Numercial value
binary
'1000.0000.0000.0001'
'1111.1100.1110.0000'
'1111.1110.0000.1100'
'0000.0000.0000.0000'
'0000.0001.1111.0100'
'0000.0011.1110.1000'
'0000.0101.1101.1100'
'0000.0111.1101.0000'
'0000.1001.1100.0100'
'0000.1011.1011.1000'
'0000.1100.1000.0000'
'0010.0001.0011.0100'
'0010.0001.0011.0100'
Process Image
1)
hex.
dec.
0x8001
-32767
0xFCE0
-800
0xFE0C
-500
0x0000
0
0x01F4
500
0x03E8
1000
0x05DC
1500
0x07D0
2000
0x09C4
2500
0x0BB8
3000
0x0C80
3200
0x2134
8500
0x2134
8500
35
Status-
LED
byte
Error
hex.
AI 1,2
0x41
on
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x42
on
0x42
on