34
Process Image

Table 27: Process Image 750-469/000-206, Type J, with broken wire diagn.

Temperature
°C
< -100.0
-100.0
-50.0
0.0
50.0
100.0
200.0
400.0
600.0
800.0
1000.0
1100.0
1200.0
> 1200.0
Broken wire
1)
Status information: X: not used, F: short-circuit, broken wire, Ü: overrange
2)
Temperature values below 0 °C are represented in two's complement binary form.
4.3

I/O Modules for Voltage Measuring (mV)

When measuring the voltage, the input range is mapped to a range of values
between -18750 and +18750. Voltage values below 0 mV are represented in two's
complement binary form.
For the measuring range ± 120 mV the resolution is 6.4 µV per digit.
Table 28: Process Image 750-469/000-003, mV measuring ±120 mV, with broken wire diagn.
Voltage
mV
< -120.0
-120.0
-90.0
-60.0
-30.0
0.0
30.0
60.0
90.0
120.0
> 120.0
1)
Voltage values below 0 mV are represented in two's complement binary form.
Numercial value
binary
XFÜ
'1111.1100.1110.0
001'
'1111.1100.1110.0
000'
'1111.1110.0111.0
000'
'0000.0000.0000.0
000'
'0000.0001.1001.0
000'
'0000.0011.0010.0
000'
'0000.0110.0100.0
000'
'0000.1100.1000.0
000'
'0001.0010.1100.0
000'
'0001.1001.0000.0
000'
'0001.1111.0100.0
000'
'0010.0010.0110.0
000'
'0010.0101.1000.0
000'
'0010.0101.1000.0
001'
'0111.1111.1111.1
010'
Numercial value
binary
'1011.0000.0000.0000'
'1011.0110.1100.0010'
'1100.1001.0001.0010'
'1101.1011.0110.0001'
'1110.1101.1011.0001'
'0000.0000.0000.0000'
'0001.0010.0101.0000'
'0010.0100.1001.1111'
'0011.0110.1110.1111'
'0100.1001.0011.1110'
'0111.1111.1111.1111'
WAGO-I/O-SYSTEM 750
750-469 2AI Thermocouple
1)
hex.
dec.
0xFCE1
-799
0xFCE0
-800
0xFE70
-400
0x0000
0
0x0190
400
0x0320
800
0x0640
1600
0x0C80
3200
0x12C0
4800
0x1900
6400
0x1F40
8000
0x2260
8800
0x2580
9600
> 0x2581
> 9601
0x7FFA
32762
1)
hex.
dec.
0xB000
-20480
0xB6C2
-18750
0xC912
-14062
0xDB61
-9375
0xEDB1
-4687
0x0000
0
0x1250
4688
0x249F
9375
0x36EF
14063
0x493E
18750
0x7FFF
32767
Status-
LED
byte
Error
hex.
AI 1, 2
0x41
on
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x42
on
0x42
on
Status-
LED
byte
Error
hex.
AI 1, 2
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
Manual
Version 1.1.0

Advertisement

Table of Contents
loading

Table of Contents