Device Description
Po
s: 26 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Anschlüsse/Leistungskontakte/Feldversorgung - Überschrift 3 @ 6\mod_1256294692864_21.doc @ 43664 @ 3 @ 1
3.2.2

Power Contacts/Field Supply

Po s: 27.1 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheitshinweise/Vorsicht/Vorsicht: Verletzungsgefahr durch scharfkantige Messerkontakte! @ 6\mod_1256193279401_21.doc @ 43414 @ @ 1
Risk of injury due to sharp-edged male contacts!
The male contacts are sharp-edged. Handle the module carefully to prevent injury.
Po
s: 27.2 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Anschlüsse/Leistungskontakte 2 LK (Messer/Feder) @ 7\mod
_1266317883167_21.doc @ 50688 @ @ 1
The I/O module 750-481/003-000 has 2 self-cleaning power jumper contacts that
supply and transmit power for the field side. The contacts on the left side of the
I/O module are designed as male contacts and the contacts on the right side as
spring contacts.

Table 4: Power jumper contacts

1
1
Figure 4: Power
jumper contacts
Po s: 27.3 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheitshinweise/Achtung/Achtung: Maximaler Strom Ex i Einspeisung 750-06xx 0,5 A / 1,0 A @ 7\mod_1274358256668_21.doc @ 56898 @ @ 1
Do not exceed maximum current via power contacts!
The maximum current available from the 750-625 Ex-i Supply Module is
500 mA.
The maximum current available from the 750-606 or 750-625/000-001 Ex-i
Supply Module is 1000 mA.
Greater currents can damage the power contacts.
When configuring the system, ensure that this current is not exceeded. If
exceeded, an additional potential feed module must be used.
Po
s: 27.4 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheitshinweise/Hinweis/Hinweis: Potentialeinspeiseklemme für Erde einsetzen! @ 3\mod_1226499037468_21.doc @ 25023 @ @ 1
Use potential feed module for Ground (earth)!
The I/O module has no power contacts for PE intake and transfer. Use a potential
feed module when a PE feed is needed for the subsequent I/O modules.
Po
s: 28 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
Connection
2
1
Blade contact
2
2
Spring contact
WAGO-I/O-SYSTEM 750
750-481/003-000 2AI RTD Ex i
Type
Number
2
2
Function
Infeed of the field
supply voltage
(U
and 0 V)
V
Forwarding of the
field supply voltage
(U
and 0 V)
V
Manual
1.1.0

Advertisement

Chapters

Table of Contents
loading

Table of Contents