Kidde Fire Protection ANTARES Manual page 86

Table of Contents

Advertisement

SYMPTOM
DEVICE ISOLATED LED
illuminated and 30 second
beep of internal sounder.
SUPPLY FAULT LED
illuminated and internal
sounder pulsing.
TM0064
POSSIBLE CAUSE
Device isolated.
1. A.C. mains failure.
2. Low battery voltage.
Page 86 of 91
ACTION
1. Using VFD assertion
devices isolated.
2. Repair/renew the device
and de-isolate.
4/2 Amp switch mode
power supply.
1. Check for 240 V 50 Hz
on the main terminal block.
2. Check F1 (5 Amp) in
terminal block.
3. Replace power supply.
4/2 Amp switch mode
power supply.
1. Check that the
BATTERY LOW LED on
the power supply is
illuminated.
2. Check battery leads for
good connection.
3. Renew batteries.
4. Replace power supply.