Kidde Fire Protection ANTARES Manual page 26

Table of Contents

Advertisement

OUTPUT SPECIFICATION
DC OUTPUT VOLTAGES
Factory set with an input voltage of 240V rms
VO1
Main O/P
VO2
Battery Charge
O/P
DC OUTPUT CURRENT
Measured with an input voltage of 240v rms.
VO1
4A Nominal 6A Max when battery charge not required
VO2
2A Max
LINE REGULATION
Measured at full load, over the specified input voltage range.
0.5% Max All Outputs.
LOAD REGULATION
VO1
50 mV MAX over the range 0 - 4A
VO2
1.5V. TYP over the range 0-1.7A
OUTPUT RIPPLE & NOISE
Measured with the PSU loaded to 160 watts at a nominal input of 240V RMS, over a bandwidth
of 0 - 30 Mhz.
Ripple - Mains & Switching
50 mV peak to peak Max ALL OUTPUTS
Noise - (Spikes)
100 mV peak to peak ALL OUTPUTS
TM0064
28V @ 4mA
+/- 0.5V
27.6V @ 5mA (Float current)
+/- 0.2V
Dropping To
26V @ Full charge current of 2A
Page 26 of 91
Issue 2.01

Advertisement

Table of Contents
loading

Table of Contents