List Loop Devices - Kidde Fire Protection ANTARES Manual

Table of Contents

Advertisement

entered the new date and time can be accepted by the ENTER/YES key. The display will return
to the option one, menu one indication.

3.2.3 List Loop Devices

This option allows the number and types of devices logged on to be displayed. The information
is displayed on the LCD/VFD and if the printer is ENABLED then a hard copy will be provided.
The option is selected from the option one menu by two presses of the CANCEL/NO key, i.e.
until the display is as shown in fig 3.2.13, and then replaced by operating the ENTER/YES key.
TUE 15 MAR 21:45 LIST LOOP DEVICES
Once entered the display will request the loop number for which the information is required,
see fig 3.2.14.
TUE 15 MAR 21:45 LIST LOOP DEVICES
The required loop number is entered and accepted, upon which the display will initially display
the number of devices connected to the loop as shown in fig 3.2.15.
TUE 15 MAR 21:45 LIST LOOP DEVICES
The number of devices is displayed for a few seconds after which the first device information is
then displayed, see fig 3.2.16. Each device is displayed for a few seconds before it is
automatically updated with the next set of data. The listing can be terminated manually by
operating the CANCEL/NO key or automatically if a fire or fault condition is reported.
Main Reception Area
ZONE 11 BREAK GLASS DO1/066 Axxx Fxxx
Where: xxx values depends on the type of device.
TM0064
Fig 3.2.13
LOOP?
Fig 3.2.14
LOOP 02 96 DEVICES
Fig 3.2.15
Fig 3.2.16
Page 49 of 91
Issue 2.01

Advertisement

Table of Contents
loading

Table of Contents