Communication LED:
Green LED - flashes when communicating with master.
HOCHIKI LED:
Amber LED - illuminated when correct personality card plugged into slave processor.
APOLLO LED:
Amber LED - illuminated when correct personality card plugged into slave processor.
NITTAN LED:
Amber LED - illuminated when correct personality card plugged into slave processor.
SUPPLY FAULT LED's
Refer to Section 1.6.

1.4.3 Outputs

Alarms outputs:
Two standard two amp outputs fully monitored to BS5839. Active until manually silenced.
Separately fused.
Auxiliary outputs:
Two sets of voltage free change-over contacts (rated 1 AMP at 30v d.c. contact). Active until
fire condition reset. (2 sets isolated via menu 1)
Fault repeat:
Common fault output capable of sinking 100 mA. Active until panel reset.
Fault relay:
1 set of volt free change-over contacts (rated 1 AMP at 30v d.c.). Active until panel reset.
Alarm Repeat:
Audible alarm output capable of sinking 100mA. Active until silence alarms.
Auxiliary repeat:
Auxiliary output capable of sinking 100mA. Active until panel reset.
Buzzer output:
Active when internal sounder operating. Capable of sinking 100mA. Steady in Fire condition.
Pulsed when alarms silenced/fault/test mode.
Manual output:
Active when manual sound alarms operated. Capable of sinking 100mA. Active until silence
alarms.
Protected Output:
TM0064
Page 20 of 91
Issue 2.01