Summary of Contents for Kidde Fire Protection ANTARES
Page 1
Exit Main Menu ANTARES MANUAL TM0064 TM0064 Page 1 of 91 Issue 2.01...
Page 2
PROPRIETARY RIGHTS NOTICE The information contained in this manual is the property of Kidde Fire Protection Services Limited and may not be reproduced or transmitted in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, nor stored in any retrieval system of any nature without the express written authority of Kidde fire Protection Services Limited.
Page 3
Preliminary Pages AMENDMENT INCORPORATION RECORD Amendment Brief Description of Content Name of Person Number Incorporating Amendment TM0064 Page 3 of 91 Issue 2.01...
Page 4
Preliminary Pages AMENDMENT INCORPORATION RECORD Amendment Brief Description of Content Name of Person Number Incorporating Amendment TM0064 Page 4 of 91 Issue 2.01...
Page 9
Preliminary Pages TABLE OF CONTENTS Chapter Page 3.2.4 List Isolated Devices 3.2.5 Select Test Mode 3.2.6 LED Test 3.2.7 Printer Status MENU TWO OPTIONS 3.3.1 Print of Event Log 3.3.2 Read a Single Device 3.3.3 Program Outputs 3.3.4 Display Checksums 3.3.5 Message Handler (Psion Only) 3.3.6 Isolate AUX Outputs 3.3.7 Change Baud Rate...
Page 10
Preliminary Pages TABLE OF CONTENTS Chapter Page 3.4.8 Clear Outputs VERIFICATION CHECKS INSTALLATION APPROVED CABLES CABLE TERMINATION AND INTERNAL ROUTINGS STATIC SENSITIVE DEVICES PANEL MOUNTING LOOP WIRING EXTERNAL WIRING LOOP WIRING TESTS POWER SUPPLY TESTS COMMISSIONING 4.9.1 Preliminary Checks 4.9.2 Voltage Tests 4.9.3 Testing Loops of Detectors 4.9.4 Testing Device Operation 4.9.5 Final Commissioning...
Page 11
Preliminary Pages TABLE OF CONTENTS Chapter Page 4.10.2 Event Printer Maintenance 4.10.3 Fault Diagnosis 4.10.4 Removal/Replacement of Assemblies 4.10.5 Routine Testing MAIN PCBS CABLE HARNESSES OPTION PCBs TM0064 Page 11 of 91 Issue 2.01...
The ANTARES is an enhanced design with many additional features and functions from its predecessors, and has been designed to meet the requirements of BS5839 1988 Part 4, Sections 1 and 2.
The SCROLL ALARMS push-button remains operable (Access level 1). FEATURES The ANTARES is configured as a two loop system giving a sensor capability of 252 or 254 devices. The device which can be accommodated by the panel are defined in the appropriate Device Manual.
1.2.2 Operator Controls Four operator controls are provided giving the following functions: SOUND ALARMS SILENCE ALARMS SYSTEM RESET SCROLL ALARMS Operator controls 1, 2 and 3 can be inhibited by the keyswitch. Operator control 4 remains operable as specified for access level 1 user operation. The 4 controls can be operated by pressing the appropriate control.
Page 15
The third menu level is used to download to the printer or display the input/output functions of the panel. This menu is accessed from the second level menu and provides the following functions: Print panel outputs. Print loop devices. Print loop outputs. Program panel outputs.
Page 16
Programmable Controlled Loop Output Device Description Devices Descriptions 1-32 Controlled from any combination of loop input device. 33-36 4 common outputs active upon operation of any input device on any loop 37-38 2 common outputs active upon operation of any input device on loop 1 39-40 2 common outputs active upon operation of any input device on loop 2 41-42...
OPTIONS 1.3.1 Integral Printer An integral printer can be connected. This is a 24 character line printer. The printer plugs directly to the display processor card and is activated by selection within the first level menu. A fire condition will always override the printer disable condition. 1.3.2 Panel Outputs Programmable By the addition of the appropriate PCB modules, 32 output (one output card set) can be obtained.
The eight special outputs are as follows: Terminals Description Output active for 6 seconds after panel reset operated. Output active for 6 seconds after silence alarms operated. Output active during LED test operated. Output when BGU is operated. Output active when a device other that a BGU is operated. Output active when more than one device in any one zone are operated.
Keypad: 12 keys: 0 to 9 numeric keys, ENTER and CANCEL control keys. ACCESS/INHIBIT switch: Keyswitch to prevent unauthorised access to all the above controls. Internal Processor fault reset: Internal push switch mounted on the Master processor control/display card to reset processor fault buzzer and LED.
Communication LED: Green LED - flashes when communicating with master. HOCHIKI LED: Amber LED - illuminated when correct personality card plugged into slave processor. APOLLO LED: Amber LED - illuminated when correct personality card plugged into slave processor. NITTAN LED: Amber LED - illuminated when correct personality card plugged into slave processor.
Volt free contacts N/O. Secure output protected against spurious operation on power up etc. Active on FIRE alarm and Sounds Alarms. Pre-alarm output: Active when Pre-alarm condition. Capably of sinking 100mA. Active until panel reset. 1.4.4 Inputs Loop 1: Four terminals for the connection of the sensor wiring, i.e. positive and negative out plus return pair.
SOUNDER CIRCUITS/POWER SUPPLIES Any cable approved by the current British Standard for "prolonged operation in a fire". Special attention should be made in selection of conductor size to ensure that a voltage drop does not prevent the devices operating within their specification even under minimum supply and maximum load condition.
Page 23
SAFETY The power supply is designed to meet the requirements of the following safety standards:- IEC 950/EN60950 Safety of Information Technology Equipment UL 1950 Electronic Data-Processing Units & Systems. RFI/EMI The power supply design aim is to meet the requirements of the following RFI/EMI standards, as a stand alone unit:- FCC 207080 Federal Communications Commission (USA) Level A...
Page 24
INPUT SPECIFICATION INPUT VOLTAGE The 14474/000 will be designed to accept a dual range input voltage. The ranges are as follows:- 90V to 132V rms, (127V to 187V peak), or 180V to 264V rms, (254V to 373V peak) The range selection is achieved by an internal manual link fitted to connector PH2: Link fitted input voltage is 90v to 132v rms Link not fitted input voltage is 180v to 264v rms This link is only accessible when the unit cover is removed.
Page 25
POWER LINE DISTURBANCES EN 54-4 Para 7.3.5 calls for the power supply to be tested to the following requirements:- Voltage Reduction 100% Duration of Reduction in half cycles (200mS) (100mS) The power supply is not provided with sufficient energy storage to withstand the voltage reductions as specified without the output voltages deviating outside of their specification limits.
Page 26
OUTPUT SPECIFICATION DC OUTPUT VOLTAGES Factory set with an input voltage of 240V rms Main O/P 28V @ 4mA +/- 0.5V Battery Charge 27.6V @ 5mA (Float current) +/- 0.2V Dropping To 26V @ Full charge current of 2A DC OUTPUT CURRENT Measured with an input voltage of 240v rms.
Page 27
SPECIAL FEATURES STANDBY OPERATION A parallel diode shall be fitted between the main and battery charge outputs to allow the externally connected battery to hold up the main output in the event of a power failure. Operational up to the maximum load current of 4A. OVERLOAD PROTECTION Protected by primary power limit at Type 110% of Max Output Power, (170W).
Page 28
The LED shall be illuminated when the incoming supply is below the specified lower operational limit, ie:- 90V, (127V peak), or 180V, (254V peak) "Regulator" Fault - Local LED Indicator, (Amber coloured) Note The sole function of the LED is to provide local indication only LED illuminated in response to output VO1 deviating outside of its operational window of 27.3 to 29.0V dc SIGNAL OUTPUTS...
Page 29
Supply Healthy - LED Drive A pair of output connections to provide the necessary drive, (LED supply current to be 8mA nominal), to supply a remote LED indicator. The LED shall be illuminated when the supply is considered to be in a healthy condition, (as specified for the Supply Fault output signal).
Page 30
Cover to be perforated sheet zinc plated and colour, (yellow), passivated. SIZE Nominal dimensions are :- 230mm (L) x 110mm (D) x 60mm (H. max) LABELLING Labels for the input and output terminals connectors, and the LED functions shall be provided upon the unit cover.
The system can accept various addresses units with any combination of these devices being connected to any single loop, the panels having loop capacities two. The ANTARES panel is based on the use of a Master Processor display/control card communicating with a two loop drive Slave Processor card.
DEVICE INDICATIONS The Slave Processor scans each address and determines which type of unit is connected at each location on each of the two loops. This data is used for subsequent scanning of the addresses in order to control and obtain information from the device correctly.
The four standard monitored sounder outputs are activated together with two sets of change-over volt-free auxiliary contacts. The internal buzzer is also activated, (constant mode). The alarm and auxiliary repeat outputs are also energised. When fitted the printer will produce a hard copy of the time of activation and the full device information, i.e.
2.3.2 Device Isolated The DEVICE ISOLATE LED is controlled via the keypad. Any loop device can be isolated or de-isolated as required, refer of the Operational Description Section. The DEVICE ISOLATE LED will be illuminated as long as there is one or more devices isolated. The devices isolated condition is also indicated by the LCD/VFD display as per section 1.4.15.
ALPHA-NUMERIC DISPLAY 2.4.1 Normal Condition The normal condition referred to as that in which the panel would normally be left, i.e. no fault or fire conditions and with the keyswitch in the INHIBIT position. TUE 15 MAR 21:45 STATUS NORMAL Fig 1.4.1 To complement the standard indications provided by the zonal and status LEDs and to display individual device information, an 80 (two line by 40) character LCD/VFD is available.
FIRE 01 Main Reception Area TOT>03 ZONE 11 BREAK GLASS DEVICE 066 LOOP 01 Fig 1.4.4 The first line of the LCD/VFD display also gives the device location message. If the panel has not been programmed the display will read LOCATION NOT ASSIGNED. Scrolling of multiple alarms is achieved using the 'Scroll Alarms' button.
2.4.6 Loop Fault SYSTEM FAULT 01 LOOP NUMBER 01 Fig 1.4.7. Should a fault occur on a loop, the display format of the LCD/VFD is as shown on fig 1.4.7. The loop number in fault is displayed. This is accompanied by the illumination of the DEVICE FAULT and SYSTEM FAULT LEDs and the internal buzzer.
Should a system alarm fault, i.e. caused by either a sounder wiring fault, of by a manual isolation of the auxiliary output the display format of the LCD/VFD is as shown on fig 1.4.10. This is accompanied by the illumination of the EXTERNAL FAULT and SYSTEM FAULT LEDs and activation of the internal buzzer.
date and time on the top line and panel status on the bottom line. TUE 15 MAR 21:45 PANEL RESET Fig 1.4.14 2.4.14 Call Engineer All fault conditions will remain indicated until a panel reset is carried out. If the fault condition still exists the fault condition will be re-activated.
POWER SUPPLY The standard integral power supply unit monitors the following fault conditions: Battery low Regulator fault Battery disconnected/charger faulty. Each of the faults are indicated by an LED. The fault output of the power supply is connected to the fault input of the panel. On the main front panel common SUPPLY HEALTHY and SYSTEM FAULT LEDs are provided, and a short fault is indicated as outlined in Sections 2.3.3 and 2.3.4.
CHAPTER 3 OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS FRONT PANEL CONTROLS 3.1.1 Access/Inhibit The ACCESS/INHIBIT keyswitch provides the means of inhibiting the four control push-buttons and the keypad, i.e. the normal functions of these four switches and the keypad are only available when the keyswitch is in the ACCESS position.
When 'TEST MODE' is selected the internal sounder will sound in the pulsed mode. This cannot be silenced under any condition. Also a test fire will not change the internal sounder to constant. In both DEVICE ISOLATED and PLEASE CALL ENGINEER modes the buzzer will bleep every 20 seconds.
The alarms will remain sounding until the 'SILENCE ALARMS' is operated. For two seconds after silencing the alarms the second line of the LCD/VFD will read ALARMS SILENCED, after which the display will return to normal. 3.1.6 Keypad The keypad is used to set up the panel initially and to provide operator functions. Three menu levels are provided, the first being directly assessable when the ACCESS/INHIBIT switch is turned to the access position.
3.1.7 Psion Option 5 of menu 2 and option 7 of menu 3 requires the use of a Psion Organiser. The Psion provides upload and download facilities. To speed up operations the Psion creates temporary files in RAM when receiving panel data. After the data is received the procedures provide the option to permanently store the files in datapacks or rampacks which must be inserted into the C drive before switching of the Psion.
TUE 15 MAR 21:45 MESSAGE HANDLER REFER TO REMOTE COMPUTER Fig 1.1.6.3 TUE 15 MAR 21:45 LOAD/SAVE PROGRAM DATA REFER TO REMOTE COMPUTER Fig 1.1.6.4 The complete set of menu options are described in Sections 3.2, 3.3 and 3.4 for Menu 2 and Menu 3 respectively.
Page 46
TUE 15 MAR 21:45 ISOLATE A DEVICE LOOP ? DEVICE Fig 3.2.2 Operation of the CANCEL/NO key will return the panel to the menu one, option one display mode. Single Device Isolate/De-isolate To isolate a single device the loop number is entered by operating the appropriate numeric keys.
Page 47
LOOP 02 DEVICE 110 DEIS? Fig 3.2.6 The action will be placed in the event log and will be printed out if the printer is enabled. When going from de-isolated to isolate status the DEVICE ISOLATED LED will be illuminated. The device can now be de-isolated by operating the ENTER/YES key or the menu reverted to the device select level by operating the CANCEL/NO key.
will also be actioned according to the resulting panel status. In both instances the display will revert to the zone select status fig 3.2.7. Operation of the CANCEL/NO key when in the zone select mode will cause the panel to revert to the first option menu one. 3.2.2 Set Time Once menu one has been entered, fig 3.2.1 the next three options can be displayed by operating the CANCEL/NO key.
entered the new date and time can be accepted by the ENTER/YES key. The display will return to the option one, menu one indication. 3.2.3 List Loop Devices This option allows the number and types of devices logged on to be displayed. The information is displayed on the LCD/VFD and if the printer is ENABLED then a hard copy will be provided.
The description displayed for types of devices, i.e. BREAK GLASS, are listed in the appropriate Device Manual. The capital letters denote the following: Loop/Device Zone Analogue value Fire threshold Isolated If a device is isolated this will be indicated on the display be a capital I on the bottom line of the display, extreme right hand character.
The panel will first request the loop number. On entering the loop number the panel will enter the test mode. If only a zone is required to be tested then, at the loop number request the ENTER/YES key is operated before entering any data. The display will now request the zone number which can be entered of the normal manner.
PRINTER ENABLED Fig 3.2.20 TUE 15 MAR 21:45 PRINTER STATUS PRINTER DISABLED Fig 3.2.21 Operating the ENTER/YES key will cause the display and hence the printer status to change its status. The display will also update accordingly. The CANCEL/NO key will revert the system on the option one display.
Fig 3.3.3 As with menu one the options can be scrolled through by operating the CANCEL/NO key. When the required option is displayed it is selected by operating the ENTER/YES key. A numeric key will return the panel to menu level one. There are seven options, six accessed by the keypad and operational on the panel, option 5 requires the Psion.
TUE 15 MAR 21:45 PRINT OF EVENT LOG EVENT LOG COMPLETED Fig 3.3.5 Any fire or fault condition occurring during the listing will automatically terminate the option, the terminate message again being generated. 3.3.2 Read a Single Device This functions allows the operator to display information for one device. When selected this option will request that the loop number be inputted.
On power up and every 24 hours the panel does a Checksum on the four main memory sections, namely the EPROM (E), the message RAM (M) and the two programmable output sections (L and P). The EPROM checksum should remain fixed unless a fault occurs but the other three areas will change as the messages are entered and the site programming is carried out.
Page 56
ARE YOU SURE? Fig 3.3.10 To prevent accidental erasure of the message memory an intermediate ARE YOU SURE ? request is made. The option can be terminated using the Psion DEL key or accepted by using the Psion EXE key. TUE 15 MAR 21:45 MESSAGE HANDLER CLEARING MESSAGE MEMORY Fig 3.3.11...
Page 57
The send option transmits a complete file of loop data to the panel. Upon selection the Psion will request whether the temporary file is to be used or one stored in the C datapack. The temporary file is one created by the Psion when data is transferred to it from the panel or from another computer.
Page 58
No more files DEL to scroll again EXE to quit Fig 3.3.17 The EXE key will revert the Psion back to the keypad mode and the panel to the 'LOOP REQUEST' level. Otherwise the files can be examined again and the required one selected. If editing has been carried out on the file, the loading of the device numbers, to the panel, will not necessarily be in numerical order.
Page 59
Upon entering the zone number the single message will be transmitted to the panel. Having transmitted the message the display will return to the display of fig 3.3.18, i.e. ready to accept a further single message. When ready to terminate the single message transmit mode, entry of device 0 will return the Psion to the keypad mode.
Enter file name PanelB Fig 3.3.24 Please note that when files are saved to C pack on the Psion a considerable wait time is involved if a datapack is used. During this period the Psion will indicate that it is copying a file. 3.3.6 Isolate AUX Outputs This option allows the isolation of the Auxillary outputs.
MENU THREE OPTIONS When the PROGRAM OUTPUTS option is selected on the menu two the LCD/VFD will change and display the PROGRAM OUTPUTS ENTERED message and then after two seconds will display the first option of menu three. TUE 15 MAR 21:45 PRINT PANEL OUTPUTS Fig 3.4.1 There are eight options available on the panel, option 7 requires the use of the Psion.
Fig 3.4.3 If there are active inputs, i.e. those with an A status, these are listed after the output number. The display scrolls automatically through the device on loop one, and then loop 2 etc,. Having completed panel output one, the system will proceed to panel output two and so on until all sixty four outputs have been listed.
O/P 122 S L 01 D058 O/P 125 S L 01 D023 O/P 112 R L 02 D067 O/P 120 S L 02 D023 THU 24 NOV 21:45 LOOP OUTPUT DEVICE LIST 3.4.3 Print Loop Outputs The sixth menu option provides the second part of the listing for the loop outputs. Having defined the output numbers this listing identifies the input devices that will activate the loop outputs.
Page 64
When the first option is selected the display will be as indicated in fig 3.4.6. The panel is requesting the output number (1 to 64) which requires to be programmed to operate on operation of specific loop input devices. The output number is entered and accepted in the usual manner. Once entered the S, which is the 'clear' status, can be actioned.
If no further devices on other loops are required for that output the CANCEL/NO key will return the display to the output number select mode. A new output can be selected and the procedure repeated. If no further outputs are required the CANCEL/NO key will return the display to the menu three option one mode.
3.4.6 Program Loop Outputs Having assigned output numbers to the necessary output devices the inputs that when activated operate them can now be programmed. This is achieved with the Program Loop Outputs option. The display for this option when selected is shown in fig 3.4.12. TUE 15 MAR 21:45 PROGRAM LOOP OUTPUTS OUTPUT ? L D ? Fig 3.4.12...
Page 67
The Psion display will list three options, Panel, Loop and Quit, see fig 3.4.15. The Quit returns the Psion to the keypad mode and the panel to menu three option one level. Selection of either Panel or Loop will cause the Psion to enter a second menu, see fig 3.4.16. 9.45P Panel Loop...
Load In the Load mode, if the loop option had been selected, an additional stage is required to determine the bank of data required, see fig 3.4.19. ENTER 1 FOR 1-64 ENTER 2 FOR 65-128 ENTER 3 FOR 129-> Fig 3.4.19 The numbers on the right refer to the outputs available.
Page 69
Loop This option is used to clear the inputs that control the loop output numbers. The normal ARE YOU SURE? message is displayed and must be accepted before the memory is cleared. A confirmation message is displayed whilst the memory is being cleared. This clear will not effect the loop devices, the outputs will still be assigned to the same loop output devices.
VERIFICATION CHECKS To ensure that the ANTARES panel is operating correctly, verification checks should be carried out a regular intervals, e.g. daily. The checks should be as follows: Carry out a buzzer, LED and loop test using the LED test option in level one menu as detailed in Section 3.2.7.
Page 71
THIS PAGE IS INTENTIONALLY BLANK TM0064 Page 71 of 91 Issue 2.01...
CHAPTER 4 INSTALLATION, COMMISSIONING AND MAINTENANCE INSTALLATION The installation of the fire detection and alarm system must comply with the current editions of: The IEE wiring regulations. The British Standard for Fire Detection and alarm systems for buildings. Care should be taken not to install the cables in close proximity to high voltage cables or in areas likely to induce electrical interference.
Satisfactory operation of the system with other cable types cannot be guaranteed especially when not wired to the appropriate regulations, i.e. loop wiring run with high voltage (A.C. mains and above) cabling. Multi-core Cables It is not permissible to run more than one detection loop in single cable, but a four core cable can be used for the feed and return of an individual loop, however, to preserve the integrity of the loop it is recommended that the feed and return have different paths around the building.
Cable Routing :- The internal cables must be kept to the absolute minimum length from the cable gland to the terminating position within the enclosure. Special attention should be made not to cross over other cables where possible as this may generate interference/electrical noise.
PANEL MOUNTING To facilitate fixing and alignment, all panels, irrespective of size, are provided with a single 'keyhole' near the top of the box and six indented mounting holes . It is not necessary to remove the backplate or outer door to mount the panel. Additional boxed power supply/ancillary equipment units can be mounted in a similar manner.
Note When using remote power supply units the connection between the control panel and the power unit represents a single supply. Failure of either the positive or negative lead will result in complete loss of power to the control panel. The a.c.
POWER SUPPLY TESTS Disconnect the batteries and make sure that the leads are suitably insulated to avoid a short condition. Disconnect the panel supply leads marked 28 V d.c. supply OUT. Connect the a.c. mains voltage to the terminal block on the switch mode power supply and perform the following tests.
Re-check that the +ve and -ve legs of each loop have a reading greater than 20 MΩ with respect to the panel earth stud. Re-check that all sounder circuits have a 4K7 resistance between the legs and that each leg has a reading greater than 20 MΩ with respect to the panel earth stud. No external wiring should be connected to the control panel PCBs.
If all is correct the VFD will display: LOGGING DEVICES. If any faults are found the panel will record a system fault, light the appropriate LEDs and display an appropriate ERROR MESSAGE. It is possible that the yellow fault lights inside the panel are illuminated.
4.9.4 Testing Device Operation Now that the detectors are all on line, check that they are all signalling back to the panel correctly. This can be done at this stage with the bells disconnected. Select Test Mode via the keypad for operation. Set off devices connected to the system, the message that there is a fire should be shown on the display and the FIRE LEDs on the front panel should light.
4.10 MAINTENANCE Maintenance of equipment extraneous to the panel is detailed in the appropriate manufacturer's literature. The back-up batteries are maintenance free. The components used in the control panels are of sufficient quality to withstand the life expectancy of the panel, of 15 years. All critical printed circuit boards are self monitoring and therefore should only be replaced as required.
Enable the a.c. mains supply to the panel. Switch the control keyswitch to ACCESS. Switch the control keyswitch to INHIBIT. 4.10.2 Event Printer Maintenance Paper Roll Replacement Use only 57-58 mm (2.25 inch), (44 mm for UCP-16), wood-free, high quality paper; maximum diameter roll 50 mm. CAUTION Ensure that paper roll replacement is not carried out in areas subject to static electricity.
Page 83
Referring to the above illustration, proceed as follows: Open the front panel to gain access to the printer. Remove the paper pivot bar by unscrewing and withdrawing the paper pivot bar. Remove any old paper and plastic roller from the paper pivot bar and discard. Prepare a fresh roll of paper by cutting a shallow "arrow head"...
Page 84
of its mounting. Release the two screws (4) and remove the printer front panel exposing the printer mechanism and black ribbon cartridge (5). Taking note of the ribbon and paper arrangement, depress the cartridge (where indicated on the cartridge). The cartridge will tip up and may then be removed and discarded.
4.10.3 Fault Diagnosis SYMPTOM POSSIBLE CAUSE ACTION PRE-ALARMED LED Analogue value of sensor 1. Clean sensor and recheck. illuminated and internal increased to a level approx. 2. Renew sensor if systems sounder pulsing. midway between normal and persists. fire threshold. DEVICE FAULT LED 1.
Page 86
SYMPTOM POSSIBLE CAUSE ACTION DEVICE ISOLATED LED Device isolated. 1. Using VFD assertion illuminated and 30 second devices isolated. beep of internal sounder. 2. Repair/renew the device and de-isolate. SUPPLY FAULT LED 1. A.C. mains failure. 4/2 Amp switch mode illuminated and internal power supply.
Page 87
SYMPTOM POSSIBLE CAUSE ACTION FIRE LEDs 1. Spurios trigger of device. 1. Press SILENCE flashing, internal sounder ALARMS. The external constant and external alarms alarms should silence and sounding. FIRE LEDs stay on constant. 2. Press SYSTEM RESET. The VFD should return to STATUS NORMAL.
4.10.4 Removal/Replacement of Assemblies It is not recommended that repairs to PCBs are carried out on site. The normal procedure would be to replace the defective unit with a spare and return the faulty unit for repair at the factory. A list of spare part numbers is provided in Spares manual. Observe static handling precautions when removing or replacing boards or other items of equipment in the panel.
Page 89
THIS PAGE IS INTENTIONALLY BLANK TM0064 Page 89 of 91 Issue 2.01...
CHAPTER 5 RECOMMENDED SPARE PARTS MAIN PCBS Table 1 lists a breakdown of spare recommended by them manufacture. DESCRIPTION PART NO. Main Processor Display/Control PCB 29-020554-000 Slave Processor PCB 29-020555-000 VFD Display PCB 43782-D004 LCD Display PCB 29-020543-000 2 Loop control PCB (Hochiki) 29-020553-000 2 Loop control PCB (Apollo) 29-020550-000...
OPTION PCB's DESCRIPTION PART NUMBER VFD Display PCB 43782-D004 LCD Display PCB 29-020543-000 rev 2 32 way output Drive PCB 29-020489-000 rev 1 32 way output Control 29-020490-000 rev 2 RS422 drive unit PCB comprising four output and one 29-020526-000 rev 1 input circuit.