Kidde Fire Protection ANTARES Manual page 69

Table of Contents

Advertisement

Loop
This option is used to clear the inputs that control the loop output numbers. The normal ARE
YOU SURE? message is displayed and must be accepted before the memory is cleared. A
confirmation message is displayed whilst the memory is being cleared.
This clear will not effect the loop devices, the outputs will still be assigned to the same loop
output devices.
Note After every programming session the panel must be left for forty seconds in order
for new checksums to be calculated. If switched off before this time checksum
errors will occur at the 4:00am data check. If is good practice to obtain a checksum
printout after every programming session for future reference.
TM0064
Page 69 of 91
Issue 2.01

Advertisement

Table of Contents
loading