Print Of Event Log - Kidde Fire Protection ANTARES Manual

Table of Contents

Advertisement

As with menu one the options can be scrolled through by operating the CANCEL/NO key. When
the required option is displayed it is selected by operating the ENTER/YES key. A numeric key
will return the panel to menu level one.
There are seven options, six accessed by the keypad and operational on the panel, option 5
requires the Psion. The options can be scrolled through using the CANCEL/NO key.
The seven options are:
1.

Print of event log.

2.
Read a single device.
3.
Program outputs
4.
Display checksums - keypad range.
5.
Message Handler - Psion only.
6.
Isolate AUX Outputs - keypad.
7.
Change Baud rate.
The function and operation of the options are described in the following sections.
3.3.1 Print of Event Log
The panel has the capacity of storing a minimum of 100 events, where an event is any fire, fault
or main panel function operation. These are stored in no-volatile RAM and are therefore retained
even in the event of total power down of the panel. When full, the event log will retain each new
event but will loose the oldest. This log can be examined by operating the ENTER/YES key
when the Print of Event Log option is displayed. If the printer is enabled the listing will be
copied to the printer as well as the display.
The events are displayed a line at a time on the second line of the LCD/VFD display. The top
line continuous to display the current date and time and the indication that the panel is still in
Print Event Log mode.
TUE 15 MAR 21:45 PRINT OF EVENT LOG
If required the listing can be aborted by operating the CANCEL/NO key. A message indicating
that the listing has been terminated will be displayed and also copied to the printer if it is enabled.
When the listing is complete a LISTING COMPLETE message will be displayed and also copied
to the printer if it is enabled.
TM0064
Fig 3.3.3
SUPPLY FAULT
Fig 3.3.4
Page 53 of 91
Issue 2.01

Advertisement

Table of Contents
loading

Table of Contents