2.4

ALPHA-NUMERIC DISPLAY

2.4.1 Normal Condition

The normal condition referred to as that in which the panel would normally be left, i.e. no fault
or fire conditions and with the keyswitch in the INHIBIT position.
TUE 15 MAR 21:45
To complement the standard indications provided by the zonal and status LEDs and to display
individual device information, an 80 (two line by 40) character LCD/VFD is available. Under
normal conditions the display shows STATUS NORMAL on the bottom line and the date and
time on the top line, with the colon located between the hours and minutes, flashing at a rate
of once every two seconds. The display format of the LCD/VFD is shown in fig 1.4.1.

2.4.2 Access condition

TUE 15 MAR 21:45
When the panel is placed in the ACCESS mode by operating the keyswitch the display will
indicate this condition as illustrated in Fig 1.4.2. The panel controls and keypad are now
accessible.

2.4.3 Fire Alarm

FIRE 01 Main Reception Area
ZONE 11 BREAK GLASS DEVICE 066 LOOP 01
When a fire alarm occurs, apart from all the other requirements of BS5839, the display
automatically identifies the device which triggered the alarm. The loop number, zone number,
device address and type of device are all displayed. After the word FIRE, the number 01 is
displayed to indicate that this is the first fire to be reported. Subsequent fires increment this
counter and also indicate in the top right hand section of the display the total number of alarms,
see fig 1.4.4. The display can be scrolled through the fires in the order in which they were
activated. The display format of the LCD/VFD for a single alarm is shown in fig 1.4.3.
TM0064
STATUS NORMAL
Fig 1.4.1
PANEL IN ACCESS
Fig 1.4.2
Fig 1.4.3
Page 35 of 91