TUE 15 MAR 21:45 PRINT OF EVENT LOG
Any fire or fault condition occurring during the listing will automatically terminate the option,
the terminate message again being generated.

3.3.2 Read a Single Device

This functions allows the operator to display information for one device. When selected this
option will request that the loop number be inputted. The display will be as indicated in fig 3.3.6.
TUE 15 MAR 21:45 READ A SINGLE DEV
After entering the loop number the display will request the device number. If the device
entered is not logged on then the DEVICE NOT CONNECTED message will be indicated for
a few seconds before returning to LOOP number request mode. If the device logged on then
the display will indicate the status of the device as shown in fig 3.3.7.
MAIN ENTRANCE HALLWAY
ZONE 01 IONISATION DO1/066 Axxx Fxxx 1
The bottom line confirms the device parameters, indicating zone, device type, (D) 01/066
(loop/device), analogue value (A), and the fire threshold value (F). When isolated an I will be
inserted on the bottom line most right of the display. The top line identifies the text message
when assigned. This display will be maintained, with the analogue value updated every scan.
To terminate the display the CANCEL/NO key must be operated. This will return the panel to
the LOOP NUMBER request mode. A further operation of the CANCEL/NO key will return the
panel to the first menu two option request display.

3.3.3 Program Outputs

This option selects the site programming and load/save routines and is itself divided into several
options. These form the options for the menu three and are detailed in section 3.4. When
selected a PROGRAM OUTPUT ENTERED message is displayed and hard copies if the printer
is enabled.

3.3.4 Display Checksums

TM0064
EVENT LOG COMPLETED
Fig 3.3.5
LOOP ? DEVICE
Fig 3.3.6
Fig 3.3.7
Page 54 of 91