The eight special outputs are as follows:
Terminals
25
Output active for 6 seconds after panel reset operated.
26
Output active for 6 seconds after silence alarms operated.
27
Output active during LED test operated.
28
Output when BGU is operated.
29
Output active when a device other that a BGU is operated.
30
Output active when more than one device in any one zone are operated.
31
Output active when more than one device is operated.
32
Output active when the panel is in test mode.
The output drive capabilities are 0 V rated at 100 mA which is the same as all the other outputs.
A manual sound alarm output is provided as standard on the main terminal card.

1.3.3 LCD/VFD Repeater

A single repeater output option is available. Various types of repeater are available:
1.
Simple LED (zonal).
2.
Zonal LED and LCD/VFD.
3.
Zonal LED, LCD/VFD and printer.
4.
Zonal output for use with mimic panel.
An interface card is required to be fitted to the panel for this option and the output is activated
by the appropriate DIL Switch 3 position 1 on the main processor card.
The interface card provides four separate output ports. Each output port is capable of multidrop
connection of repeaters, i.e. up to 10 repeaters can be connected to the one output port. A twisted
pair data cable is required. If a repeater requires control, i.e. SILENCE ALARMS, SYSTEMS
RESET etc., then a twin twisted pair data cable must be used, i.e UL 2439 or Beldon 9729.
1.4

PANEL CONTROLS AND OUTPUTS

1.4.1 Controls

Front Panels
Four manual switches:
Standard fire alarm control functions. SILENCE ALARMS, SYSTEM RESET, SOUND
ALARMS AND SCROLL ALARMS.
TM0064
Description
Page 18 of 91