1.3

OPTIONS

1.3.1 Integral Printer

An integral printer can be connected. This is a 24 character line printer. The printer plugs
directly to the display processor card and is activated by selection within the first level menu.
A fire condition will always override the printer disable condition.

1.3.2 Panel Outputs

Programmable
By the addition of the appropriate PCB modules, 32 output (one output card set) can be obtained.
By the use of the remote computer these can be programmed, such that any output can be
operated on the activation of any loop input device. Each output can be set, during programming,
to de-activate on either silence alarms of panel reset. Once programmed a printout of the active
devices can be obtained.
The outputs are switched negative when active and are capable of driving remote LED indicators
or relays. If volt free contacts or monitored sounder outputs are required the appropriate output
module is required.
Zonal, Loop and Special Outputs
On the standard panel the addition of the necessary output card set, (one set per 32 outputs), will
provide 20 zonal outputs, 2 loop outputs and 8 special outputs.
The zonal outputs (terminals 1-20) work in conjunction with the appropriate zonal LED
indicators, i.e. any device activated in that zone will activate the appropriate output. The outputs
once activated will remain active until the panel is reset.
The loop outputs (terminals 21-22) are active when any device on that loop is activated. As with
zonal outputs these will remain active until the panel is reset.
Terminals
1-20
Zonal outputs
21-22
Loop outputs
TM0064
Description
Page 17 of 91
Issue 2.01