4 Wiring and Connection
4.6.2 Connecting a Dynamic Brake Unit
• Using NC Contacts for the Dynamic Brake Contactor
24 V
∗ The above figure is for using a dynamic brake contactor with NC contacts. The dynamic
brake answer signal (a signal from NC auxiliary contacts) is input to CN1-45. To indicate an
error if the input signal to CN1-45 turns OFF (open) while the dynamic brake is activated, the
Pn515 parameter in the multi-winding drive unit must be set to n.E. If the dynamic
brake answer signal is not used, Pn515 is set to n.8 (default setting).
Note: 1. If you assign more than one signal to the same input circuit, OR logic will be used
4-28
SERVOPACK
CN1
47
45*
DU
DV
DW
CN115
DB
DB24
DBON
0 V
DB
and any of the input signals will cause the circuit to operate. This may result in unex-
pected operation.
2. The maximum current for DB24 and DBON is 300 mA.
Dynamic brake contactor
(Auxiliary contacts)
Main circuit surge
absorption unit
Coil surge
absorption unit
For I/O
power supply
24 V
0 V
Dynamic brake resistor