7
LON plug-in module
7.1
E3I040 I bus/LON plug-in module
Item
Component
1
'S3' programming switch: I bus ad-
dress
2
'R60' resistor: 'LON bus' terminator
resistor
3
'X30' bridge: Ground fault monitoring
'LON bus'
Building Technologies
Fire Safety
Preparation
Set in accordance with system documentation
If the LON bus is wired as free topology, 'R60' must
be changed to 50 ς, see description in document
001260
For ground fault monitoring –> see page 37
Set according to description in document 001260,
'Programming ground fault monitoring' chapter
3
X30
1
S3
2
R60
LON plug-in module
Default ex factory
Address 0
100 ς
Removed (inactive)
008726_e_en_--
06.2017
21