DVC 310 installation and commissioning
instructions 4189340917 UK
2.3 Wiring and terminals
2.3.1 Wiring diagram
The numbers in the diagram above indicate the following:
1 Power
AREP: Yellow wire on X2 - red wire on Z1 - green wire on X1 - black wire on Z2
PMG: X2, X1 and Z2
Shunt: X1 and X2
10 A fast-blow fuses externally mounted must be used in the three cases
2 Field excitation
The field winding + to the terminal F+
The field winding - to the terminal F-
3 Battery
Ensure the polarity is correct when connecting
The battery supply must be protected by a 1 A slow-blow fuse