CGC 200 installation and commissioning
instructions 4189340806 UK
Digital input
Switch
Common
0 V
dc
The digital inputs require DC voltage. AC voltage will damage the controller.
2.2.4 List of terminal connections
The power supply, inputs and outputs are connected to the CGC 200 terminals. CGC 200 also has a USB B-
socket for connecting to a PC. The terminal connections are listed in the following table.
No.
Name
1
+
2
-
3
MPU Input
4
Input 1
5
Input 2
6
Emergency Stop Input
3
7
Input 4
8
Input 5
9
Gens L
10
Gens N
11
Fuel Output
12
Start Output
13
Config. Output1
14
Config. Output2
15
Config. Output3
USB USB Service Port
DEIF A/S
Type
Power supply +
Power supply -
RPM input
Digital input
Digital input
Digital input
Digital input
Digital input
Generator voltage L1
Generator neutral
Relay output (normally open) Run coil
Relay output (normally open) Starter (crank)
Relay output (normally open) Configurable
Relay output (normally open) Configurable
Relay output (normally open) Configurable
USB B female connection
Details
8 to 35 V
dc
Ground
Magnetic pickup, or tacho generator
Coolant temperature switch, or configura-
ble
Low oil pressure switch, or configurable
Emergency stop input (Auxiliary)
Remote start, or configurable
Configurable
Generator voltage measurement
Generator voltage measurement
For connection to a PC
Installation
Page 8 of 32

Advertisement

Table of Contents
loading

Table of Contents