Deif CGC 200 Installation And Commissioning Instructions page 14

Compact genset controller
Hide thumbs Also See for CGC 200:
Table of Contents

Advertisement

CGC 200 installation and commissioning
instructions 4189340806 UK
Param-
Parameter
eter
name
num-
ber
P40
Running detect.
P41
Remove starter
RPM
P42
Remove starter
Hz
*You can fill in the values chosen for your system.
DEIF A/S
Range
De-
fault
value
0 to 2
2
0 to 3000
360
RPM
10.0 to 30.0
14.0
Hz
Value
Description
chos-
en*
0: RPM
1: Genset frequency
2: RPM and frequency (running detec-
tion is present when the value required
to remove the starter is met for either
engine speed (see P41) or genset fre-
quency (see P42))
For RPM, P13 and P41 must be de-
fined.
For frequency, P42 must be defined.
Minimum engine speed required for re-
moval of the starter and running detec-
tion
Minimum genset frequency required for
removal of the starter and running de-
tection
Commissioning
Page 14 of 32