CGC 200 installation and commissioning
instructions 4189340806 UK
Param-
Parameter
eter
name
num-
ber
P19
G RPM >
P20
G f <
P21
G f >
P22
Running feed-
back timer
P23
U > aux. term.1
P24
U < aux. term.1
P25
Relay 01
P26
Relay 02
P27
Relay 03
P28
Digital input 1
P29
Digital input 1
timer
P30
Digital input 2
P31
Digital input 2
timer
P32
Digital input 3
P33
Digital input 3
timer
P34
Digital input 4
P35
Digital input 4
timer
P36
Digital input 5
P37
Digital input 5
timer
P38
Default genset
mode
P39
Display pass-
word
DEIF A/S
Range
De-
fault
value
0 to 6000
1710
RPM
0 to 75.0 Hz
45.0
0 to 75.0 Hz
57.0
0 to 20.0 s
5.0
12.0 to 40.0 V
33.0
4.0 to 30.0 V
8.0
0 to 6
4
0 to 6
1
0 to 6
2
0 to 10
5
0 to 20.0 s
10.0
0 to 10
6
0 to 20.0 s
2.0
0 to 10
4
0 to 20.0 s
1.0
0 to 10
2
0 to 20.0 s
3.0
0 to 10
1
0 to 20.0 s
10.0
0 to 2
0
0 to 9999
2000
Value
Description
chos-
en*
Generator over-speed protection, if run-
ning detection (see P40) is RPM input
only
Generator under-frequency protection
Generator over-frequency protection
Maximum allowable time for running de-
tection (see P40)
High battery supply voltage
Low battery supply voltage
See Table 1: Configurable output func-
tions
See Table 2: Configurable input func-
tions
0: Stop mode
1: Manual start
2: Auto start
Prevents unauthorised changes to pa-
rameters using the controller front panel
Commissioning