Bender ISOMETER IRDH575 Manual page 61

Insulation monitoring device for it ac and dc systems with integrated test generator and controller for eds46..., eds47... and eds49... systems
Table of Contents

Advertisement

Operation and setting
Type of sup-
ply system
DC
AC
3AC
* = Set the response value of EDS460/490 to < 5 mA
(See EDS460/490 manual, Chap. 6.6.3.2)
** = Set the response value of EDS461/491 to < 0.5 mA
(See EDS460/490 manual, Chap. 6.6.3.2)
Test current limiting for supply systems < 40 V
IRDH575_D00089_05_M_XXEN/01.2020
EDS470
min.
10 mA
25 mA
25 mA
Please note:
In supply systems to be monitored with a voltage < 40 V the
maximum test current of all IRDH575B1... versions is
limited to approximately 25 mA .
max.
min.
25 mA
1 mA
25 mA
2.5 mA
25 mA
2.5 mA
EDS473
max.
2.5 mA
2.5 mA
2.5 mA
62