Bender ISOMETER IRDH575 Manual page 31

Insulation monitoring device for it ac and dc systems with integrated test generator and controller for eds46..., eds47... and eds49... systems
Table of Contents

Advertisement

Connection
Legend to wiring diagram :
For external indicating instrument:
1
current output 0...20 mA or 4...20 mA
External TEST button (NO contact)
*2
External RESET button (NC contact or wire jumper),
*3
(with the terminals open and the ISO-SETUP menu set to Memory: off,
insulation fault alarms will not be stored).
STANDBY
*4
When the contact is closed, insulation measurement does not take place;
system disconnection
S1 = ON : RS-485 interface (A/B) is terminated with 120 Ω resistor
5
S2 = unassigned)
Serial interface RS-485 (A/B)
6
System fault relay K3 (device fault and EDS Alarm) (Addr.: 1);
7
N/C operation (fixed setting)
Alarm relay K2 (insulation fault 2); changeover contacts provided
8
Alarm relay K1 (insulation fault 1); changeover contacts provided
9
Supply voltage U
10
For UL and CSA applications, the use of 5 A fuses is mandatory
Connection to the 3 AC system to be monitored:
11
connect terminals L1, L2, L3 to conductor L1, L2, L3
Connection to the AC system to be monitored:
12
terminal L1 to conductor L1and
terminal L2, L3 to conductor L2
Connection to the DC system to be monitored:
13
terminal L1 to conductor L+ and
terminals L2, L3 to conductor L-
14
Separate connection of
*
The terminal pairs 2, 3 and 4 must be wired so that they are
galvanically isolated and must not have a connection to PE.
IRDH575_D00089_05_M_XXEN/01.2020
(see nameplate) via 6 A;
S
and KE to PE
32