Operation

The configuration of the device includes 2 steps:
Setting the input type and output type with the DIP switches on the device
Configuration and setting of diagnostic functions with PC control program
6.1

Configuration on the device

Set the input type with DIP switch SW1 on the device side.
Select the input type (potential-free contact, proximity switch, magnetic encoder, current signal or
voltage signal)
Select the base threshold for a magnetic encoder (50 mV or 500 mV)
Set the output type with DIP switch SW2 on the device side.
Select the output type (current sink, current source, voltage),
Select the voltage output range (0 V ... 5 V or 0 V ... 10 V).
Configuring the device:
Dismount the device (see section 9.1).
Select the input type from the table (see figure).
Adjust the input type using DIP switch SW1.
If necessary, select the base threshold for magnetic encoders.
Select the output type from the table (see figure).
Adjust the output type using DIP switch SW2.
If necessary, select the voltage output range.
Mount the device (see section 5.1).
The device is configured.