Wire the SD500-ARM as shown in Figure 4.47.
4.15.5 Using a MR-201/T Control Relay From Air Products
When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override
trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Current: 15 mA max.
Operating Voltage: 24 VDC nominal
Resistance: 4 K
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Supervised
Power Limited
Figure 4.47 Polarity Reversal Connection Using the SD500-ARM Module
Intended for Connection to a
Polarity Reversal Circuit of A
Remote Station Receiving Unit
Having Compatible Rating.
EOL
Control Panel Installation
To Remote
Receiving Station
55