Answering Machine Bypass
This option is used in conjunction with HFSS Honeywell Fire Software Suite. This feature ensures that an answering machine will not
interfere with communication between the panel and the computer. If an answering machine is used at the panel site, enable this feature;
if an answering machine is not used, disable the feature. This option is factory-programmed as No (disabled). The selection made here
must match the programming for this option in the Communication Configuration dialog box of HFSS.
13. Select Y (answering machine bypass enabled) or N (answering machine bypass disabled) by pressing the up or down arrow key,
then press ENTER.
Phone Line Unused
This option is used so that you can set unused phones lines to "Yes", so no auto-test will be sent through that line.
This option is factory programmed as No.
14. Select Y or N by pressing the up or down arrow key, then press ENTER.

Edit Ethernet

1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
5.
Select 3 for Edit Ethernet.

AlarmNet Timers

1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
5.
Select 4 for AlarmNet Timers.
6.
The available options for AlarmNet Timers are as follows: *default
• Ethernet: None, 75 seconds, 90 seconds, 3 minutes, *5 minutes, 1 hour, 24 hours, 30 days.
• Cellular: None, *24 hours, 30 days
• Old Alarm: None, 10 minutes, 15 Minutes,*30 Minutes, 1 Hour, 2 Hours, 4 Hours, 6 Hours, 12 Hours,
24 Hours

Phone Line Gains

1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Figure 9.7 Edit Ethernet Message
Figure 9.8 AlarmNet Timers
Programming
109