3: Nfpa 72 Polarity Reversal; Using The 5220 Module - Honeywell 6808 Installation And Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Control Panel Installation
It is not possible to reset the remote indication until you clear the condition and reset the control panel.
4.15.3 NFPA 72 Polarity Reversal
NOTE: Intended for connection to a polarity reversal circuit of a control unit at the protected premises having compatible rating.

Using the 5220 Module

When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override
trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition.
Standby Current: 100 mA, 24 VDC
Alarm: 100 mA, 24 VDC
To install the 5220 for polarity reversal, follow the steps below:
1.
Locate the knockout on the right side of the control panel cabinet to connect the 5220 using a short piece of conduit (must not
exceed 20 feet in length).
2.
Wire the 5220 to the control panel using the four-wire pigtail provided as shown in 4.45. This diagram also shows how to connect
the 5220 to the remote indicator. Do not install an EOL resistor in the terminals of the NAC circuit used for this application.
3.
Connect earth ground wire to the 5220 chassis with mounting screw.
52
Intended for connection to a Polarity
Reversal circuit of a Remote Station
receiving unit having compatible ratings.
Note:
NAC Circuit 2 Used
as an example.
Any NAC circuit
could be used.
Non-Supervised
Non-Power Limited
Note: The shunt connection is recognized only as a
supplementary signaling unit as part of a local control
unit and is not recognized as an auxiliary control unit
connection per NFPA 72.
Figure 4.44 City Box Connection
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017

Advertisement

Table of Contents
loading

Table of Contents