Current Draw Worksheet For Sd Slc Devices - Honeywell 6808 Installation And Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

2.
The FACP can only support 5 devices w/LED's on. This current draw has been added to the panels alarm current.
3.
SK-Beam-T draws a maximum of 500 mA from Auxiliary power only when the test feature is used. This should be considered
when determining auxiliary power capacity but not calculated into current requirements for day to day operation.
4.
power is removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.
5.
Use next size battery with capacity greater than required.
6.
Total does not include isolator devices or accessory bases.

Current Draw Worksheet for SD SLC Devices

Use Table 3.3 to determine current requirements during alarm/battery standby operation when SD SLC devices are installed. You can
install up to 127 SD devices per panel.
For each device use this formula:
Fire Panel (Current draw from
battery)
Addressable SLC Devices
SD500-AIM
SD500-MIM
SD500-ARM
SD500-PS
SD505-HEAT
SD505-PHOTO
SD500-ANM
SD500-SDM
SLC Accessory Bases
SD505-6RB
SD505-6SB
SD505-DUCTR
SD505-DTS-K
SD505-DUCT
SLC Isolator Devices
SD500-LIM
SD505-6IB
Accessories Modules
6860 Remote LCD Annunciator
5860 Remote LCD Annunciator
6855 Remote LCD Annunciator
5824 Serial/Parallel Printer
Interface
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
If using door holders, you do not need to consider door holder current for alarm/battery standby, because
5
Number of
Device
Devices
This column
1
(100 max)
(50 max.)
(12 max)
(4 max.)
Table 3.3 Current Draw worksheet for SD Devices
Current per Device
X
This column
=
Standby:
Alarm:
Standby/Alarm:
Aux. Pwr
Standby:
Alarm:
SLC
Standby/Alarm:
SLC
Standby/Alarm:
Aux. Pwr
Standby:
Alarm:
Standby/Alarm:
Aux. Pwr
Standby:
Alarm:
SLC
Standby/Alarm:
Aux. Pwr
Standby:
Alarm:
SLC
Standby/Alarm:
None, included with SD505-DUCTR worst case.
SLC
Standby/Alarm:
Standby/Alarm:
Standby:
Alarm:
Standby
Alarm
Standby:
Alarm:
Standby/Alarm:
Before You Begin Installing
Standby
Alarm
Current
Current
Current per number of devices.
190 mA 190 mA
250 mA
250 mA
1
.55 mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
8 mA mA
60 mA
mA
55 mA mA
mA
.55 mA mA
mA
20 mA mA
106 mA
mA
.082 mA mA
mA
1 mA mA
32 mA
mA
.082 mA mA
mA
2
20 mA
mA
2
62 mA
mA
.5 mA mA
mA
.5 mA mA
mA
.092 mA mA
mA
20 mA mA
25 mA
mA
20mA mA
25 mA
mA
20 mA mA
25 mA
mA
45 mA mA
mA
23