4.
Press the up or down arrows to select the desired module. Refer to Section 8.5 for available choices. Press ENTER.
5.
Enter the point number. Press ENTER.
6.
Press the up or down arrows to select the type (Notification or unused). Press ENTER.
7.
Press the up or down arrows to select the desired Group. Press ENTER.
8.
Edit module name. See Appendix B, or press right arrow to skip point name edit.

9.6 System Options

This section of the manual explains how to customize software options that affect general operation of the system. This includes such
items as: Communication Options, Daytime/Nighttime Sensitivity, Holiday Days, Time Options, Miscellaneous Options, Daylight Sav-
ing Options, Edit Banner, and SLC Family. Refer to each individual subsection for complete instructions.
9.6.1 Communication Options

Auto Test Time

To access the Auto Test Time screen:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
5.
Select 1 for Auto Test Time.
6.
Enter the hour you desire the control panel to send an automatic test report (or press the up or down arrow key), then press ENTER.
7.
Enter the minutes (or press the up or down arrow key), then press ENTER.
8.
Select AM or PM by pressing the up or down arrow key, then press ENTER.
9.
Select Report Time Interval by pressing the up or down arrow key, then press ENTER. Time Interval selections are 24hr, 12hr, 6hr
and 4 hr.
NOTE: AM and PM are only available if the panel "Clock Options" are set for AMPM mode. Otherwise the clock is in military time and AMPM is
not selectable.

Phone Lines

To access the phone lines screen:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
5.
Select 2 for the phone Lines.