How to enable/disable an IO line

How to enable/disable an IO line
These operations are not applicable for a Vigilon Plus Network Node.
NA
An interface input/output line can be disabled or enabled. You will need to
know the IO line, device and loop numbers, these numbers can be found
in the site specific documents held by the person responsible for the fire
system.
An output line of an interface unit may be assigned
to a sector and can only be disabled by disabling that
sector. This has the effect of also disabling all other
devices in the sector.
a. Press the MENU ON/OFF button.
b. Press the F1 button to select [Control].
c. Press the F4 button to select [UserCode]. At the flashing cursor using
the keypad input your PIN code and then press the Enter button.
d. To disable an IO line press the F2 button to select [Disable] or press
the F1 button to select [Enable], the display reads 'Enable' or 'Disable'.
e. Press the F2 button to select [IO Line]. At the flashing cursor using the
keypad input an IO line number.
f. Press the F2 button to select [Device]. At the flashing cursor using the
keypad input a device number from a range 1 to 200.
g. Press the F2 button to select [Loop]. At the flashing cursor using the
keypad input a loop number from a range 1 to 6.
h. Press the F2 button to select [Enter]. Notice the action has been
processed and a message appears on the display: 'IO line disabled/
enabled at Card n'. The disablement light will illuminate upon
disablement of an IO line.
28
www.acornfiresecurity.com
www.acornfiresecurity.com

How to enable/disable auxiliary relay

The control panel / network node has two
auxiliary relays that provides voltage free contacts
to control external equipment in the event of a fire
or fault condition. The operation of the relays can
be disabled or enabled.
a. Press the MENU ON/OFF button.
b. Press the F1 button to select [Control].
c. Press the F4 button to select [UserCode].
At the flashing cursor using the keypad input
your PIN code and then press the Enter
button.
d. To disable the auxiliary relay press the F2
button to select [Disable] or press the F1
button to select [Enable]. This puts 'Disable'
or 'Enable' on the display.
e. Press the F4 button three times selecting
<etc> on each occasion and then press the
F2 button to select [Aux Rly]. At the flashing
cursor using the keypad input an auxiliary
relay number from a range 1 to 2.
f. Press the F2 button to select [Enter].
Notice the action has been processed and a
message appears on the display: 'Aux Rly n
disabled/enabled'. The Disablement light will
illuminate upon disablement of an auxiliary
relay.