System Operation
The control panel can be in one of seven conditions at any given moment: Normal, Alarm, Prealarm, Supervisory, Trouble, Silenced, and
Reset. Table 10.1 describes the behavior of the panel in each of these modes.
Operation
Occurs When
Mode
No alarm,
supervisory or
trouble con-
dition exists
and menus are
not in use.
Normal
A smoke
detector goes
into alarm or a
pull station is
activated.
Alarm
CO detector
goes into
alarm.
If more than 3
categories are
active at a
single time this
screen will
display.
120
System Behavior
SYSTEM POWER LED is on.
The All Systems Normal display indicates
that the system is in normal mode.
The current date and time display on the
last line of the LCD.
The communicator seizes control of the
phone line and calls the central station.
The on-board annunciator sounds a loud,
steady beep (any notification devices
attached to the system will also sound).
GENERAL ALARM LED flashes.
The LCD displays a screen similar to this
one.
Table 10.1 Operation Mode Behavior
In This Mode You Can
Enter the appropriate code, or rotate the key to
activate the Main Menu.
Press the down arrow to view the alarm. A screen
similar to this one displays.
Press SILENCE and enter an access code (or activate
the key) to silence the annunciator (and any
notification devices attached to the system).
When the alarm condition clears, press RESET and
enter a code (or activate the key) to restore the panel
to normal.