System Operation
The communicator is not allowed to be reset when alarms or supervisories are active. Communicator reset is not allowed if any of the
following are active:
Fire Alarm
Fire Supervisory
Fire Pre-Alarm
CO Alarm
CO Supervisory
10.4.11 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72.
If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL TRBLE condition. A detector enters a
CAL MAINT state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
When a CAL TRBLE condition occurs, the central station receives a detector trouble report ("373" and the zone or point for Contact ID
format; "FT" and the zone or point in SIA format).
To check sensitivity for an individual detector, follow the steps below. Section 8 provides instructions for printing the status of all detec-
tors in the system.
1.
From the Main Menu, press 2 for Point Functions.
2.
Press 2 for Point Status.
3.
Select the module where the point you want to check is located.
4.
Enter the number of the point you want to check and press ENTER.
5.
A screen similar to those shown in Figure 10.3 will display.
You can print detector status by uploading the detector status to and printing from HFSS Honeywell Fire Software Suite.
10.4.12 View Status of a Point
1.
From the Main Menu, select 2 for Point Functions.
2.
Select 2 for Point Status
3.
From the list that displays, press ENTER to select the module where this point is located. Next, enter the point to display. The
screen that displays will show you if the point has a trouble and will provide sensitivity compliance information. (See Section
10.4.11 for complete information about detector sensitivity compliance.)
10.4.13 View Alarms or Troubles
When the system is in alarm or trouble, you can press down arrow to view the location of an alarm or trouble.
118
Figure 10.3 Checking Detector Sensitivity Compliance
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017