4.15.6 Transmitter Activated by Dry Contacts
This section describes the connection of a UL 864 listed remote station transmitter to the 6808 FACP dry contacts. The FACP contacts
must be supervised by the remote station transmitter module using end-of-line resistors (ELRs) with a value determined by the transmit-
ter manufacturer. Power is also provided by the remote station transmitter manufacturer. Refer to the remote station transmitter manufac-
turer's manual for details.
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Figure 4.49 Transmitter Activated by Dry Contact
Control Panel Installation
57