4.2 AC Connection

At installation, connect the AC terminals to the power source as shown in Figure 4.2. It may be necessary for a professional electrician to
make this connection.
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGES
Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated
!
equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
The AC terminals are rated at 120 VAC, 60 Hz, 3.6A.

4.3 Battery Power

The batteries must be sealed lead acid type. Before connecting the batteries to the FACP, make certain that the interconnect cable
between the batteries is not connected. Do not connect the battery jumper cable until the system is completely installed. Observe polarity
when connecting the batteries
WARNING: RISK OF PERSONAL INJURY
!
Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with
sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention
The control panel battery charge capacity is 7.0 to 35 AH. The main control cabinet can house batteries up to 18 AH, larger capacity bat-
teries can be housed in a RBB (see Section 4.3.1 for details). Use 12V batteries of the same AH rating. Determine the correct AH rating
as per your current load calculation (see Section 3.7).
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Figure 4.2 120VAC Power Connection
Control Panel Installation
27