NOTE: For assistance with SBUS calculation, please refer to www.silentknight.com.
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
370 feet maximum using 22 Gauge wire
938 feet maximum using 18 Gauge wire
1493 feet maximum using 16 Gauge wire
2362 feet maximum using 14 Gauge wire
4.4.2 Wiring Configurations
Figure 4.8 illustrates Class B configurations wiring.
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
= 2 x .100 amps
= 1 x .010 amps
= 1 x .200 amps
= 1 x .040 amps
Figure 4.8 SBUS Class B Wiring
Control Panel Installation
= .200 amps
= .010 amps
= .200 amps
= .040 amps
= .450 amps
Supervised
Power Limited