Honeywell 6808 Installation And Operation Manual page 104

Addressable fire alarm control panel
Table of Contents

Advertisement

Programming
Type Selection
SWITCH
SWITCH
(cont.)
104
Function
Latching Option
MAN_PULL
WATERFLOW
SUPERVISORY
Non Latching
FIRE DRILL
SILENCE
RESET
PAS_ACK
Latching
ZN_AUX1
Non Latching
Latching
ZN_AUX2
Non Latching
Latching
SYS_AUX1
Non Latching
Latching
SYS_AUX2
Non Latching
DETECT SW
Latching
TAMPER
Non Latching
MAN REL
ILOCK
CO DETECT SW
CO SUPERVISORY DETECT SW
STATUS PT
Table 9.2 SLC Point Programming
Comments
Use this switch type for manual pull stations. This input is
always latched. The switch can clear only when an alarm is
reset.
Use this switch type for monitoring water flow in a sprinkler
system. Switch closure will cause a sprinkler alarm. Water
flow switches can be programmed as latching or non-latching.
You can program a delay of up to 90 seconds to be used with
a water flow switch. The delay allows for normal, brief
changes in sprinkler system water pressure. The water flow
alarm will not activate unless the switch is active for the
programmed delay time.
Waterflow delay of the FACP and the waterflow device shall
not exceed 90 seconds.
If a delay is used, the system begins counting down when the
switch closes. If the switch opens (restores) before the timer
expires, a water flow alarm is not generated. If the water flow
switch remains closed after the timer expires, a water flow
alarm will be generated.
Use this switch type for tamper monitoring of sprinklers and
other fire protection devices. If a contact closes, a sprinkler
supervisory event will be generated. Supervisory switches can
be latching or non-latching.
System-level, non latching switch. This switch is an alternative
way of causing a fire drill. It has the same operation as the fire
drill option available from the annunciator. When the switch is
activated, a fire drill begins; when the switch is de-activated, a
fire drill ends.
System-level switch provides an alternate way to silence the
system; same effect as pressing the Silence key.
System-level switch provides an alternate way to reset the
system; same effect as pressing the Reset key.
Positive acknowledge switch. This switch must be used in
zones programmed as Positive Alarm Sequence (see
Table 9.1).
If an acknowledge switch closes when an alarm or trouble
condition is not already in progress, a trouble will occur.
You must use a UL listed normally open, momentary switch
type. The switch must be rated at 5V, 100 mA (minimum) and
be used with an EOL resistor for supervision.
Use these switch types if you want to monitor special zone-
level conditions (such as operation of a fan or damper).
Use these switch types if you want to monitor special system-
wide conditions (such as operation of a fan or damper).
Used to monitor conventional 4-wire detectors, a contact
closure will generate a detector alarm event.
Performs identically to a supervisory switch, but will be
indicated as a tamper switch on the LCD annunciator.
Manual release switch, typically a pull station.
Interlock release switch input.
CO Detector Switch
CO Supervisory Detector Switch
Status Point Switch
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017

Advertisement

Table of Contents
loading

Table of Contents