FUNCTION
CHARACTERISTICS
1 contact controlled by
Siren
Max 2A resistive 30 Vdc, NA-NC
General Alarm
refer to basic board topography
(
General Fault
Max 2A resistive 30 Vdc, NA-NC
refer to basic board topography
(
USR1
Max 2A resistive 30 Vdc, NA-NC
refer to basic board topography
(
USR2
Max 2A resistive 30 Vdc, NA-NC
refer to basic board topography
(
EN54-2 8.8
EN54
General Fault Output
!
Contact range: max 30 VAC/DC, 2A,
Non-inductive loads
Selection of type of contact (Normally open or
Normally closed) through JGST Jumper on
board (refer to basic board topography)
EN54-2 7.7
EN54
General Alarm Output
!
Contact range: max 30 VAC/DC, 2A,
Non-inductive loads
Selection of type of contact (Normally open or
Normally closed) through JALL Jumper on board
(refer to basic board topography)
EN54-2 7.7
EN54
Outputs
!
USR1and USR2
Contact range: max 30 VAC/DC, 2A,
Non-inductive loads
Selection of type of contact (Normally open or
Normally closed) through JURS1 e JUSR2
Jumpers on board (refer to basic board
topography)
NOTE:
To program the activation of these outputs refer
to "Am-8000 Programming Manual"
PAGE - 10
NOTIFIER ITALIA

Relay outputs

24Vcc / 2A resistive
selectable through Jumper JALL
)
selectable through Jumper
)
selectable through Jumper
)
selectable through Jumper
)
The General Fault relay is usually in energized state. It is de-energized in Fault
condition.
NOTE: do not connect to this output any alarm remote control, such as a
telephone dial (EN 54.2. 7.7) because the output line is not controlled
The main Alarm relay is available in free voltage contacts
NOTE: do not connect to this output any alarm remote control, such as a telephone
dial (EN 54. 2. 7.7) because the output line is not controlled.
The USR1 and USR2 relays are available in free voltage contacts
NOTE: do not connect to this output any alarm remote control, such as a telephone
dial (EN 54. 2. 7.7) because the output line is not controlled.
Manuale di installazione
Doc. 160.1-AM8000-ITA Rev A.3
JGST
JUSR1
JUSR2
CNU
19 20
NC/ NO
COM
Main Fault output connections
(refer to basic board topography)
CNU
21 22
NC/ NO
COM
Main Alarm output connections
(refer to basic board topography)
CNU
USR1
23 24
NC/ NO
COM
NC/ NO
URS1 e USR2 output connections
(refer to basic board topography)
CNU
USR2
25 26
COM
AM-8000