•
Fire Supervisory
•
Fire Pre-Alarm
•
CO Alarm
•
CO Supervisory
•
EVS Alarm
•
EVS Supervisory
10.4.10 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72. Detectors are
sampled every three hours.
If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a Calibration Trouble condition. A detector enters
a Calibration Maintenance state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
When a Calibration Trouble condition occurs, the central station receives a detector trouble report ("373" + Zone # for Contact ID for-
mat; "FT" + Zone # in SIA format).
To check sensitivity for an individual detector, follow the steps below.
1.
From the Main Menu, press 2 for Point Functions.
2.
Press 2 for Point Status.
3.
Select the module where the point you want to check is located.
4.
Enter the number of the point you want to check and press ENTER.
A screen similar to those shown in Figure 10.5 will display for 6820 and Figure 10.6 for 6820EVS.
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
Figure 10.5 Checking Detector Sensitivity Compliance 6820 4x20 display
139