Fig. 24 El2014 "Process Data" Tab - Beckhoff EL2124 Documentation

Digital output terminals
Table of Contents

Advertisement

Product overview, digital output terminals
Fig. 24: EL2014 "Process Data" tab
A Selection of the diagnostic scope via the selection dialog "Predefined PDO Assignment"
B Display of (optional) PDOs (process data objects)
C Selection of the required Sync Manager
D Display of the PDOs available for selection
Three pre-defined PDO assignments can be selected:
• Full Diagnostics:
Inputs: Selection of the PDOs 0x1A00 (diagnostics per channel) and 0x1A02 (device diagnostics). Both
the diagnostic data for each channel and the data for the device diagnostics are displayed and
transmitted.
Outputs: PDO 0x1600 (switching state of the outputs) is displayed and transmitted.
• Compact Diagnostics:
Inputs: Selection of the PDO 0x1A02 (device diagnostics). Only the diagnostic data for the device are
displayed in the System Manager and transmitted to the control system.
Outputs: PDO 0x1600 (switching state of the outputs) is displayed and transmitted.
• No Diagnostics: Neither 0x1A00 nor 0x1A02 is selected. No diagnostic data are displayed in the
System Manager and none are transmitted to the control system.
Outputs: PDO 0x1600 (switching state of the outputs) is displayed and transmitted.
Compact Diagnostics, No Diagnostics
When converting from "Full Diagnostics" to "Compact Diagnostics" or "No Diagnostics", or when de-
activating the PDO 0x1600, links already established to the deactivated objects are deleted.