El2042 - Technical Data - Beckhoff EL2124 Documentation

Digital output terminals
Table of Contents

Advertisement

Product overview, digital output terminals
2.5.1

EL2042 - Technical data

Technical data
Number of outputs
Reverse voltage protection
Load type
Nominal output voltage
Switching times
Output current max. per channel
Supply voltage for electronic
Current consumption of power contacts
Current consumption via E-bus
Electrical isolation
Bit width in the process image
Configuration
Weight
Permissible ambient temperature range during operation
Permissible ambient temperature range during storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 72]
Vibration/shock resistance
EMC resistance burst/ESD
Protection class
Installation position
Approval
52
EL2042
2
yes
ohmic, inductive, lamp load
24 V
(-15% / +20%)
DC
T
: 40 µs typ.; T
200 µs typ.
ON
OFF
max. 4 A (short-circuit-proof) per channel, 8 A with parallel connec-
tion
via the E-Bus
typ. 13 mA + load
typ. 120 mA
500 V (E-bus/field voltage)
2 output bits
no address setting, configuration via TwinCAT System Manager
approx. 55 g
0°C ... + 55°C
-25°C ... + 85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
according to EN 60068-2-6/EN 60068-2-27,
see also Installation instructions for terminals with increased me-
chanical load capacity [} 74]
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE
Version: 5.2