El2014 - Technical Data - Beckhoff EL2124 Documentation

Digital output terminals
Table of Contents

Advertisement

Product overview, digital output terminals
2.2.2

EL2014 - Technical data

Technical data
Connection technology
digital outputs
Rated load voltage
Load type
Distributed clocks
Max. output current
Short circuit current
Breaking energy
Output stage
Reverse voltage protection
Switching times
Supply voltage for electronic
Current consumption via E-bus
Recommended cycle time
Current consumption of power contacts typ. 15 mA + load
Electrical isolation
Bit width in process image
Supports NoCoeStorage [} 68] function
Configuration
Conductor types
Special features
Weight
Permissible ambient temperature range
during operation
Permissible ambient temperature range
during storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 72]
Vibration/shock resistance
EMC immunity/emission
Protection class
Installation position
Approval
24
EL2014
1-wire
4
24 V
(-15% / +20%)
DC
ohmic, inductive, lamp load
No
0.5 A (short-circuit-proof) per channel
< 1 A typ.
< 150 mJ/channel
push (high-side switch)
Yes
T
: 50 µs typ., T
: 100 µs typ.
ON
OFF
Via the power contacts
typ. 60 mA
≥ 200 µs; with cycle times < 200 µs the process data is not
updated in each cycle.
500 V (E-bus/field voltage)
4-bit output and 20-bit diagnostics
Yes
via System Manager
solid wire, stranded wire and ferrule
diagnostics via process data and LED: overtemperature,
PowerFail, short circuit (per channel)
approx. 70 g
0 °C ... +55 °C
-25 °C ... +85 °C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE,
IECEx
Version: 5.2
EL20xx, EL2124

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents