Beckhoff EL2124 Documentation page 35

Digital output terminals
Table of Contents

Advertisement

2.2.6.1
Restore object
Index 1011 Restore default parameters
Index (hex) Name
1011:0
Restore default param-
eters [} 162]
1011:01
SubIndex 001
2.2.6.2
Configuration data
Index 80n0 DIG Safe State Active Ch.n
(n=0 for Ch.1 to n=3 for Ch.4)
Index (hex) Name
80n0:0
DIG Safe State Active
Ch.n
80n0:01
Active [} 33]
Index 80n1 DIG Safe State Value Ch.n
(n=0 for Ch.1 to n=3 for Ch.4)
Index (hex) Name
80n1:0
DIG Safe State Value
Ch.n
80n1:01
Value [} 33]
2.2.6.3
Command object
Index FB00 DIG Command
Index (hex) Name
FB00:0
DIG Command
FB00:01
Request
FB00:02
Status
FB00:03
Response
EL20xx, EL2124
Meaning
Restore default parameters
If this object is set to "0x64616F6C" in the set value
dialog, all backup objects are reset to their delivery
state.
Meaning
Maximum subindex
Enabling of the output state defined in index 0x80n1:01
in case of a bus error
0: output retains its current state.
1: output is switched to the state defined in index
0x80n1.
Meaning
Maximum subindex
Defines the state of the output in case of a bus error:
0: output off
1: output on
Meaning
Maximum subindex
reserved
reserved
reserved
Version: 5.2
Product overview, digital output terminals
Data type
Flags
UINT8
RO
UINT32
RW
Data type
Flags
UINT8
RO
BOOLEAN
RW
Data type
Flags
UINT8
RO
BOOLEAN
RW
Data type
Flags
UINT8
RO
OCTET -
RW
STRING[2]
UINT8
RO
OCTET -
RO
STRING[4]
Default value
0x01 (1
)
dec
0x00000000
(0
)
dec
Default value
0x01 (1
)
dec
0x01 (1
)
dec
Default value
0x01 (1
)
dec
0x00 (0
)
dec
Default value
0x03 (3
)
dec
{0}
0x00 (0
)
dec
{0}
35

Hide quick links:

Advertisement

Table of Contents
loading