El2022, El2024, El2024-0010 - Technical Data - Beckhoff EL2124 Documentation

Digital output terminals
Table of Contents

Advertisement

Product overview, digital output terminals
2.3.1

EL2022, EL2024, EL2024-0010 - Technical data

Technical data
Number of outputs
Non-reactive outputs
Reverse voltage protection
Load type
Nominal output voltage
Switching times
Output current max. per channel
Switch-off energy (inductive)
Current consumption from load voltage
Supply voltage for electronic
Current consumption via E-bus
Electrical isolation
Bit width in the process image
Configuration
Weight
Permissible ambient temperature range
during operation
Permissible ambient temperature range
during storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 72]
Vibration/shock resistance
EMC resistance burst/ESD
Protection class
Installation position
Approval
44
EL2022
2
-
yes
ohmic, inductive, lamp load
24 V
(-15% / +20%)
DC
T
: 40 µs typ.; T
: 200 µs typ.
ON
OFF
max. 2 A (short-circuit-proof)
< 1,7 J/channel
typ. 9 mA + load
via the E-Bus
typ. 100 mA
500 V (E-bus/field voltage)
2 output bits
no address setting, configuration via TwinCAT System Manager
approx. 55 g
-25°C ... +60°C (extended temperature range)**
-40°C ... +85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
according to EN 60068-2-6/EN 60068-2-27,
see also Installation instructions for terminals with increased mechanical load capacity
[} 74]
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE
cULus [} 150]
ATEX [} 82]
IECEx
Version: 5.2
EL2024
4
yes
(see notice [} 13])
typ. 13 mA + load
typ. 120 mA
4 output bits
CE
cULus [} 150]
ATEX [} 82]
EL2024-0010
-
12 V
(-15% / +20%)
DC
0°C ... + 55°C*
-25°C ... + 85°C
CE
cULus [} 150]
ATEX [} 81]
EL20xx, EL2124