El2002, El2004, El2008 - Technical Data - Beckhoff EL2124 Documentation

Digital output terminals
Table of Contents

Advertisement

2.1.1

EL2002, EL2004, EL2008 - Technical data

Technical data
Number of outputs
Non-reactive outputs
Load type
Nominal output voltage
Switching times
Output current per channel
Switch-off energy (inductive)
Current consumption from load
voltage (power contacts)
Supply voltage for electronic
Current consumption via E-bus
Electrical isolation
Bit width in the process image
Configuration
Weight
Permissible ambient temperature
range during operation
Permissible ambient temperature
range during storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 72]
Vibration/shock resistance
EMC resistance burst/ESD
Protection class
Installation position
Approval
EL20xx, EL2124
EL2002
EL2004
2
4
-
yes
(see notice [} 13])
ohmic, inductive, lamp load
24 V
(-15% / +20%)
DC
T
: 60 µs typ.; T
: 300 µs typ.
ON
OFF
maximum 0.5 A (short-circuit proof)
max. 150 mJ/channel
typ. 15 mA
via the E-Bus
typ. 100 mA
typ. 100 mA
500 V (E-bus/field voltage)
2 output bits
4 output bits
no address setting, configuration via TwinCAT System Manager
approx. 55 g
-25°C ... +60°C (extended temperature
range)
-40°C ... +85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
according to EN 60068-2-6/EN 60068-2-27,
see also Installation instructions for terminals with increased mechanical load capacity [} 74]
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
variable
CE
cULus [} 150]
ATEX [} 82]
Version: 5.2
Product overview, digital output terminals
EL2008
8
yes
(see notice [} 13])
typ. 110 mA
8 output bits
Aligned in horizontal installation position:
-25°C ... +60°C (extended temperature range)
All other installation positions, see note
[} 78]: -25°C ... +45°C
see note [} 78]