Product overview, digital output terminals
2.4.1

EL2032, EL2034 - Technical data

Technical data
Number of outputs
Reverse voltage protection
Load type
Rated voltage of the outputs
Switching times
Output current max. per channel
Short circuit and open circuit detection
Switch-off energy (inductive)
Current consumption from load voltage
Supply voltage for electronic
Current consumption via E-bus
Electrical isolation
Bit width in the process image
Configuration
Weight
Permissible ambient temperature range dur-
ing operation
Permissible ambient temperature range dur-
ing storage
Permissible relative humidity
Dimensions (W x H x D)
Mounting [} 72]
Vibration/shock resistance
EMC resistance burst/ESD
Protection class
Installation position
Approval
48
EL2032
2
yes
ohmic, inductive, lamp load
24 V
(-15% / +20%)
DC
T
: 40 µs typ.; T
: 200 µs typ.
ON
OFF
max. 2 A (short-circuit-proof)
yes; open circuit detection [} 47] from approx. 1 A regular output current
< 1,7 J/channel
typ. 12 mA + load
via E-Bus
typ. 100 mA
500 V (E-bus/field voltage)
2 output bits, 2 input bits (diagnostic)
no address setting, configuration via TwinCAT System Manager
approx. 55 g
-25°C ... +60°C (extended temperature range)
-40°C ... +85°C
95%, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
according to EN 60068-2-6/EN 60068-2-27,
see also Installation instructions for terminals with increased mechanical load capacity
[} 74]
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE
cULus [} 150]
ATEX [} 82]
Version: 5.2
EL2034
4
typ. 14 mA + load
typ. 120 mA
4 output bits, 4 input bits (diagnostic)