Specifications; Electrical Data, 380-480 - Danfoss VLT AutomationDrive FC 361 Series Design Manual

90–315 kw, enclosure sizes j8–j9
Hide thumbs Also See for VLT AutomationDrive FC 361 Series:
Table of Contents

Advertisement

Specifications

5 Specifications
5.1 Electrical Data, 380-480 V
®
VLT
AutomationDrive FC 361
High/normal overload
(High overload=150% current during 60 s, normal
overload=110% current during 60 s)
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
5
5
Enclosure size
Output current (3-phase)
Continuous (at 400 V) [A]
Intermittent (60 s overload) (at 400 V) [A]
Continuous (at 460 V) [A]
Intermittent (60 s overload) (at 460 V) [kVA]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Maximum input current
Continuous (at 400 V) [A]
Continuous (at 460 V) [A]
Maximum number and size of cables per phase
Mains and motor [mm
Maximum external mains fuses [A]
Estimated power loss at 400 V [W]
Estimated power loss at 460 V [W]
3)
Efficiency
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Weight, enclosure protection rating IP20 kg (lbs)
Efficiency
3)
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Table 5.1 Electrical Data for Enclosures J8, Mains Supply 3x380–480 V AC
1) For fuse ratings, see chapter 7.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 5.4 Ambient Conditions. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
16
VLT® AutomationDrive FC 361
2
(AWG)]
1)
2), 3)
2), 3)
Danfoss A/S © 03/2019 All rights reserved.
N90K
N110
NO
HO
NO
90
90
110
125
125
150
177
177
212
195
266
233
160
160
190
176
240
209
123
123
147
127
127
151
171
171
204
154
154
183
2x95 (2x3/0)
315
315
2031
2031
2559
1828
1828
2261
± 15% (tolerance relates to variety in voltage and cable conditions). These
N132
N160
HO
NO
HO
110
132
132
150
200
200
J8
212
260
260
318
286
390
190
240
240
285
264
360
147
180
180
151
191
191
204
251
251
183
231
231
350
400
2289
2954
2923
2051
2724
2089
0.98
0–590
110 (230)
98 (216)
0.98
0–590
110 (230)
75 (167)
NO
160
250
315
347
302
332
218
241
304
291
3770
3628
MG06K102