Danfoss VLT AutomationDrive FC 361 Series Design Manual page 39

90–315 kw, enclosure sizes j8–j9
Hide thumbs Also See for VLT AutomationDrive FC 361 Series:
Table of Contents

Advertisement

Mechanical Installation Con...
6.6.3 Derating for Ambient Temperature and Switching Frequency
NOTICE
FACTORY DERATING
Danfoss drives are already derated for operational temperature (55 °C (131 °F) T
Use the graphs in Table 6.3 to determine if the output current must be derated based on switching frequency and ambient
temperature. When referring to the graphs, I
switching frequency.
Enclosure Switching
pattern
J8–J9
60 AVM
110
380–480 V
100
90
80
70
60
0
SFAVM
110
100
90
80
70
60
0
Table 6.3 Derating Tables for Drives Rated 380–480 V
MG06K102
Design Guide
indicates the percentage of rated output current, and fsw indicates the
out
High overload HO, 150%
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
1
2
3
4
5
6
7
8
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
1
2
3
4
5
Danfoss A/S © 03/2019 All rights reserved.
and 50 °C (122 °F) T
AMB,MAX
Normal overload NO, 110%
110
100
90
80
70
60
50
9
0
1
2
3
110
100
90
80
70
60
50
6
0
1
2
).
AMB,AVG
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
4
5
6
7
8
9
40 ˚C (104 ˚F)
45 ˚C (113 ˚F)
50 ˚C (122 ˚F)
55 ˚C (131 ˚F)
3
4
5
6
37
6
6